Medium-Voltage Power Cable ® Electric Utility PowrPak Underground PILC Replacement Cable Copper EPR Insulation Flat Strap Concentric Neutral LLDPE Jacket Temperature Rating: • Normal ............................. 105°C • Emergency* ...................... 140°C • Short Circuit ..................... 250°C * Operation at the emergency overload temperature shall not exceed 1500 hours cumulative during the lifetime of the cable. Standards and Specifications: PowrPak® cables meet the latest ANSI/ICEA S-94-649 and AEIC CS8 specifications for Ethylene Propylene Rubber (EPR) insulated concentric neutral cable except for dimensional requirements. Applications: PowrPak® cables are intended for use in dry or wet locations for today's aging and expanding urban underground distribution systems of utilities where PILC has been used previously. It is specifically designed to be used in urban underground network systems where existing duct space is limited. Options: • Class C copper conductors • Reduced insulation wall thickness • BIFILL® blocked conductor and cable core/ jacket. Tested in accordance with ICEA T-34-664 • Available with lead-free EAM insulation • Dry nitrogen cure • Red stripes on jacket • Deformation-resistant polypropylene jacket • 3 X 1/C triplex or parallel • CSA C68.5 For information on conductor sizes or voltage ratings not shown in the tables, contact your General Cable sales representative or e-mail [email protected]. STRAPS 12 14 16 14 16 14 NO. THKN. (mils) 20 20 20 25 25 35 WIDTH (mils) 175 175 175 175 175 200 FAULT CURRENT CAPABILITY OF FLAT STRAP NEUTRAL CROSS- SECTIONAL AREA (kcmil) 3 53.466 62.377 71.288 77.971 89.110 124.754 AMPERES FOR FAULT DURATION (CYCLES) 6 8 15,064 10,652 9,225 17,574 12,427 10,762 10 8,251 9,626 12 7,532 8,787 20,085 14,202 12,300 11,001 10,043 21,968 15,534 13,453 12,032 10,984 15 6,737 7,850 8,982 9,824 20 25,106 17,753 15,374 13,751 12,553 11,228 35,149 24,854 21,524 19,252 17,574 15,719 13,613 5,834 6,807 7,779 8,508 9,724 34 Amperes