SPEC 6155 September, 2016 Uniblend PVC High Speed ® EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 5 kV and 8 kV, UL Type MV-105, 133%/100% Ins. Levels, 115 Mils Features (cont’d.): • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C • 105°C rating for continuous operation • 140°C rating for emergency overload conditions • 250°C rating for short circuit conditions Product Construction: Conductor: • 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand Extruded Strand Shield (ESS): • Extruded thermoset semi-conducting stress- control layer over conductor Insulation: • Lead-free Ethylene Propylene Rubber (EPR) insulation, contrasting in color to the black semi-conducting shield layers Extruded Insulation Shield (EIS): • Thermoset semi-conducting polymeric layer free stripping from insulation Metallic Shield: • 5 mil annealed copper tape with an overlap of 25% Jacket: • Low-friction, lead-free, flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC) Options: • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 Applications: • Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial three-phase applications • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4(A)(5) Features: • Rated at 105˚C • High Speed low friction technology for easy cable pulling • Excellent heat, moisture and sunlight resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength CATALOG NUMBER 17001.120605 17001.120405 17001.120205 17001.120105* 17001.125105 17001.125205 SI2/0ZE (AWG/ kcmil) 6 4 2 1 1/0 2/0 17001.125305* 3/0 17001.135405 17001.136005 17001.136205 17001.136505 17001.137005 4/0 250 350 500 750 17001.637505 1000 COND. CONDUCTOR DIAMETER INCHES 0.17 0.22 0.27 0.31 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06 NOMINAL INSULATION DIAMETER INCHES THICKNESS NOMINAL JACKET NOMINAL CABLE DIAMETER WEIGHT COPPER WEIGHT CONDUIT IN AIR (1) Compliances: • National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC, UL File # E90501 • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA Acceptable • RoHS Compliant Packaging: • Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing AMPACITY UNDERGROUND DUCT (2) 0.415 0.490 0.060 1.52 0.65 16.51 0.455 0.535 0.060 1.52 0.70 17.15 0.510 0.590 0.060 1.52 0.76 19.05 0.545 0.620 0.060 1.52 0.79 20.07 0.580 0.655 0.060 1.52 0.82 21.08 0.620 0.695 0.060 1.52 0.86 22.10 0.665 0.745 0.080 2.03 0.94 24.38 0.720 0.795 0.080 2.03 1.00 25.65 0.770 0.850 0.080 2.03 1.05 27.18 0.870 0.945 0.080 2.03 1.14 29.72 0.990 1.065 0.080 2.03 1.27 33.53 1.170 1.250 0.080 2.03 1.45 38.35 1.320 1.400 0.080 2.03 1.60 42.42 MIN. MAX. INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km 90˚C 105˚C 90˚C 5 kV AND 8 kV, UL TYPE MV-105, 133%/100% INS. LEVELS, 115 MILS 295 365 471 539 623 728 886 1053 1199 1559 2088 2962 3815 439 543 701 802 927 1083 1318 1567 1784 2320 3107 4407 5677 126 178 259 315 386 474 585 725 849 1165 1639 2427 3210 188 83 93 90 265 110 120 115 385 150 165 155 468 170 190 175 575 195 215 200 706 225 255 230 871 260 290 260 1080 295 330 295 1263 330 365 325 1735 395 440 390 2439 480 535 465 3611 585 655 565 4777 675 755 640 105˚C 97 125 165 185 215 245 275 315 345 TRAY (3) 90˚C 105˚C - - - - - - - - 195 220 225 250 260 290 300 335 335 370 415 415 460 500 610 690 515 575 665 745 795 890 SIZING (4) (INCHES) 2 2.5 2.5 2.5 3 3 3 3 3.5 3.5 4 5 5 Dimensions and weights are nominal; subject to industry tolerances. * Non-stock item; minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310.60(C)(73) of the NEC for triplexed or three single conductor copper cables in isolated conduit in air based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310.60(C)(77) of the NEC for triplexed or three single conductor copper cables in underground ducts (three conductors per duct), based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392.80(B)(2) of the NEC at an ambient air temperature of 40˚C (104˚F); the ampacities are based on 75% of the values per Table 310.60(C)(69), operating temperature denoted in column header. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 70% of the values per Table 310.60(C)(69). (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered but should be checked for individual installations. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE”. b) The NESC Lightning bolt symbol is on all Uniblend® constructions. CONDUIT Phone: 888-593-3355 www.generalcable.com