SPEC 6355 September, 2016 Uniblend PVC High Speed ® EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 15 kV, UL Type MV-105, 133% Ins. Level, 220 Mils Product Construction: Conductor: • 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand Extruded Strand Shield (ESS): • Extruded thermoset semi-conducting stress- control layer over conductor Insulation: • Lead-free Ethylene Propylene Rubber (EPR) insulation, contrasting in color to the black semi-conducting shield layers Extruded Insulation Shield (EIS): • Thermoset semi-conducting polymeric layer free stripping from insulation Metallic Shield: • 5 mil annealed copper tape with an overlap of 25% Jacket: • Low-friction, lead-free, flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC) Options: • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 Applications: • Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial three-phase applications CATALOG NUMBER 17031.130205 17031.130105* 17031.135105 17031.135205 17031.135305* 17031.135405 17031.136005 17031.136205 17031.136505 17031.137005 17031.137505 (AWG/ kcmil) 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000 COND. SIZE CONDUCTOR DIAMETER INCHES 0.27 0.31 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 1.06 NOMINAL INSULATION DIAMETER INCHES MIN. MAX. Applications (cont'd.): • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4(A)(5) Features: • Rated at 105˚C • High Speed low friction technology for easy cable pulling • Excellent heat, moisture and sunlight resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C • 105°C rating for continuous operation • 140°C rating for emergency overload conditions • 250°C rating for short circuit conditions NOMINAL CABLE NOMINAL JACKET THICKNESS DIAMETER WEIGHT COPPER WEIGHT 0.710 0.800 0.080 0.745 0.830 0.080 0.780 0.865 0.080 0.820 0.905 0.080 0.865 0.955 0.080 0.920 1.005 0.080 0.970 1.060 0.080 1.070 1.155 0.080 1.190 1.275 0.080 1.370 1.460 0.080 1.520 1.610 0.110 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.03 2.79 , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS 0.99 25.14 1.02 25.91 1.06 26.92 1.10 27.94 1.14 28.95 1.21 30.73 1.25 31.75 1.35 34.29 1.47 37.34 1.65 41.91 1.86 47.24 Dimensions and weights are nominal. Subject to industry tolerances. * Non-stock item; minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310.60(C)(73) of the NEC for triplexed or three single conductor copper cables in isolated conduit in air based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310.60(C)(77) of the NEC for triplexed or three single conductor copper cables in underground ducts (three conductors per duct), based on a conductor temperature of 90˚C (194 ˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392.80(B)(2) of the NEC at an ambient air temperature of 40˚C (104˚F) the ampacities are based on 75% of the values per Table 310.60(C)(69), operating temperature denoted in column header. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 70% of the values per Table 310.60(C)(69). (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered but should be checked for individual installations. ¥ 100% insulation level is available upon request. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE”. b) The NESC Lightning bolt symbol is on all Uniblend® constructions. 658 733 825 938 1078 1261 1407 1783 2331 3234 4219 979 1090 1228 1396 1604 1876 2093 2653 3468 4812 6278 276 332 403 492 603 743 866 1184 1657 2445 3228 CONDUIT IN AIR (1) Compliances: • National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC, UL File # E90501 • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA Acceptable • RoHS Compliant Packaging: • Material cut to length and shipped on non- returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing AMPACITY UNDERGROUND DUCT (2) INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km 90˚C 105˚C 90˚C 15 kV¥ 411 150 165 494 170 190 600 195 215 732 225 255 897 260 290 1105 295 330 1289 330 365 1761 395 440 2466 480 535 3638 585 655 4803 675 755 155 175 200 230 260 295 325 390 465 565 640 TRAY (3) 105˚C 90˚C 105˚C 165 185 215 - - - - 195 220 245 225 250 275 260 290 315 300 335 345 335 370 415 415 460 500 515 575 610 665 745 690 795 890 SIZING (4) (INCHES) 3 3.5 3.5 3.5 3.5 4 4 5 5 6 6 CONDUIT Phone: 888-593-3355 www.generalcable.com