SPEC 6475 September, 2016 Uniblend CPE High Speed ® EPR/Copper Tape Shield with Overall CPE Jacket, Medium-Voltage Power, Shielded 15 kV, UL Type MV-105, 133% Ins. Level, 220 Mils, Three Conductor Product Construction: Conductor: • 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand Extruded Strand Shield (ESS): • Extruded thermoset semi-conducting stress- control layer over conductor Insulation: • Lead-free Ethylene Propylene Rubber (EPR) insulation, contrasting in color to the black semi-conducting shield layers Extruded Insulation Shield (EIS): • Thermoset semi-conducting polymeric layer free stripping from insulation Metallic Shield: • 5 mil annealed copper tape with an overlap of 25% Grounding Conductor: • 1 bare grounding conductor may be in contact with metallic shielding tape Overall Jacket: • Flame-retardant, moisture- and sunlight-resistant Chlorinated Polyethylene (CPE) Options: • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 Applications: • Suited for use in a broad range of commercial, industrial and utility applications, where reliability is the major concern, space is limited and ease of installation is critical • In wet or dry locations when installed in accordance with NEC • In aerial, direct burial, conduit, open tray and underground duct installations Features: • Rated at 105˚C • Excellent flame resistance – burns to an ash; does not exhibit thermoplastic drip • Excellent heat, moisture and sunlight resistance • Outstanding corona resistance • Flexibility for easy handling • High Speed low friction technology for easy cable pulling CATALOG NUMBER 15593.440205* 15593.445105* 15593.445205* 15593.445405* (AWG/ kcmil) 2 1/0 2/0 4/0 15593.446005* 250 15593.446205* 350 15593.446505* 500 15593.447005* 750 15593.447505* 1000 COND. SIZE CONDUCTOR DIAMETER INCHES 0.27 0.34 0.38 0.48 0.53 0.62 0.74 0.91 NOMINAL INSULATION DIAMETER INCHES MIN. MAX. 0.710 0.800 0.780 0.865 0.820 0.905 0.920 1.005 0.970 1.060 1.070 1.155 1.190 1.275 1.370 1.460 1.06 1.520 1.610 NOMINAL CABLE GROUND WIRE (AWG) 15 kV¥ 4 4 3 2 2 1 1/0 2/0 NOMINAL JACKET THICKNESS DIAMETER WEIGHT COPPER WEIGHT CONDUIT IN AIR (1) Features (cont’d.): • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C • 105°C rating for continuous operation • 140°C rating for emergency overload conditions • 250°C rating for short circuit conditions Compliances: • National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC, UL File # E90501 • UL 1685 (70,000 BTU/hr) • OSHA Acceptable • RoHS Compliant Optional Flame Tests: • IEEE 1202 (70,000 BTU/hr)/CSA FT4 Packaging: • Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing AMPACITY UNDERGROUND DUCT (2) INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km 90˚C 105˚C 90˚C , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS, THREE CONDUCTOR 6 0.110 0.110 0.110 0.110 0.110 0.110 0.140 0.140 0.140 2.79 2.79 2.79 2.79 2.79 2.79 3.56 3.56 Dimensions and weights are nominal. Subject to industry tolerances. * Non-stock item; minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310.60(C)(75) of the NEC for three conductor copper cable in isolated conduit in air based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310.60(C)(79) of the NEC for three conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on three conductor Type MV-105 cables in single layer in an uncovered tray with maintained spacing of not less than one cable diameter between cables, in accordance with Section 392.80(B)(1) of the NEC at an ambient air temperature of 40˚C (104˚F); the ampacities are per Table 310.60(C)(71), operating temperature denoted in column header. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 95% of the values in NEC Table 310.60(C)(75). ¥ 100% insulation level is available upon request. Note: a) All sizes are “FOR CT USE”. b) The NESC Lightning bolt symbol is on all Uniblend® constructions. 2.04 2.20 2.30 2.52 2.66 2.94 3.21 3.61 51.82 55.88 58.42 64.01 67.56 74.68 81.53 91.69 3.56 3.99 101.35 2226 2811 3163 4203 3313 4183 4707 6255 4775 7106 6182 7686 9200 10978 13983 11438 16337 20810 1343 1609 2398 2812 3766 5244 7682 10124 913 1358 145 165 1998 195 215 2394 220 245 3567 290 320 4184 315 350 5604 385 430 7803 470 525 150 195 220 285 310 375 450 11431 570 635 545 15064 650 725 615 TRAY (3) 105˚C 90˚C 105˚C 160 165 185 210 235 305 215 240 245 275 325 360 335 360 400 400 435 490 485 535 600 585 660 670 745 770 860 Phone: 888-593-3355 www.generalcable.com 3/2017