SPEC 7400 September, 2016 Duralox Uniblend ® Conductors: • 1/0 AWG thru 750 kcmil bare, copper compact Class B strand Extruded Strand Shield (ESS): • Thermoset semi-conducting extruded stress control layer over conductor Insulation: • Lead-free Ethylene Propylene Rubber (EPR) insulation, contrasting in color to the black semi-conducting shield layers Extruded Insulation Shield (EIS): • Thermoset semi-conducting polymeric layer free stripping from insulation Shield: • 5 mil annealed copper tape with a minimum 25% overlap Ground: • Annealed bare copper Class B stranding per ASTM B8 Armor: • Aluminum Interlocked Armor (AIA) Jacket: • Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), red Options: • Galvanized Steel Interlocked Armor (GSIA) Applications: • Ideally suited for use in a broad range of commercial, industrial and utility applications where reliability is the major concern, maximum performance is demanded, space is limited, ease of installation is critical and fire resistance is necessary CATALOG NUMBER 17480.535100* 17480.535200* 17480.535400* 17480.536000* 17480.536200* 17480.536500* 17480.537000* COND. NO. OF (AWG/) kcmil COND. SIZE INCHES INCHES mm INCHES mm (AWG) INCHES mm INCHES mm INCHES mm 1/0 AWG - 750 kcmil CONDUCTORS 35 kV, 100% INS. LEVEL, 345 MILS INS. 3 1/0 0.34 1.02 25.9 1.12 28.4 4 2.77 70.4 0.075 1.91 2.93 74.5 1419 2113 4063 6050 3 2/0 0.38 1.06 26.9 1.16 29.5 4 2.86 72.6 0.075 1.91 3.02 76.7 1687 2512 4441 6613 3 4/0 0.48 1.16 29.5 1.26 32.0 3 3.08 78.2 0.075 1.91 3.24 82.3 2482 3696 5572 8297 3 250 0.53 1.21 30.7 1.32 33.4 2 3.19 81.1 0.085 2.16 3.38 85.7 2856 4253 6165 9180 3 350 0.62 1.31 33.3 1.41 35.8 2 3.40 86.3 0.085 2.16 3.58 91.0 3858 5745 7499 11166 3 500 0.74 1.43 36.3 1.53 38.9 1 3.66 93.0 0.085 2.16 3.83 97.3 5344 7957 9400 13997 3 750 0.91 1.61 40.9 1.71 43.4 2/0 4.05 102.9 0.085 2.16 4.23 107.5 7805 11622 12843 19123 Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item; minimum runs apply. Please consult Customer Service for price and delivery. COND. DIA. MIN. Applications (cont'd.): • Installed in wet or dry locations, indoors or outdoors, direct burial and in exposed or concealed work • May be used in cable trays or on approved support in protected areas • Permitted for use per NEC Article 330 - Class I, Division 2 - Class II, Division 2 - Class III, Divisions 1 and 2 Features: • Rated at 105˚C wet or dry • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical- and radiation-resistant • Excellent crush resistance • Cost-effective alternative to installations in conduit • Meets cold bend test at -40˚C • 105°C rating for continuous operation • 140°C rating for emergency overload conditions • 250°C rating for short circuit conditions • Sunlight-resistant for CT use Compliances: Industry Compliances: • UL 1072 • ICEA S-93-639/NEMA WC74 • AEIC CS8 • UL Type MV-105, UL File # E90501 • UL Type MC, UL File # E90496 Flame Test Compliances: • IEEE 383 (70,000 BTU/hr) • UL 1685 (70,000 BTU/hr) • IEEE 1202 (70,000 BTU/hr) CSA FT4 • ICEA T-29-520 (210,000 BTU/hr) • ICEA T-30-520 (70,000 BTU/hr) Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA Acceptable • RoHS Compliant Packaging: • Material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing ® EPR/AIA/PVC, Power, Shielded, Armored 35 kV, UL Type MV-105 or MC, 100% Ins. Level, 345 Mils, Three Conductor Product Construction: INSULATION DIAMETER GRND. WIRE SIZE MAX. NOM. DIA. (OVER) ARMOR THICKNESS NOMINAL JACKET NOMINAL CABLE O.D. COPPER WEIGHT 1000 FT LBS/ kg/ km NET WEIGHT W/AL ARMOR 1000 FT LBS/ kg/ km Phone: 888-593-3355 www.generalcable.com