SPEC 6360 September, 2016 Aluminum Uniblend PVC High Speed ® EPR/Copper Tape Shield/PVC, Medium-Voltage Power, Shielded 15 kV, UL Type MV-105, 133% Ins. Level, 220 Mils Features (cont'd.): • Meets cold bend test at -35˚C • 105°C rating for continuous operation • 140°C rating for emergency overload conditions • 250°C rating for short circuit conditions Product Construction: Conductor: • 2 AWG thru 1000 kcmil 1350 aluminum compact Class B strand Extruded Strand Shield (ESS): • Extruded thermoset semi-conducting stress- control layer over conductor Insulation: • Lead-free Ethylene Propylene Rubber (EPR) insulation, contrasting in color to the black semi-conducting shield layers Extruded Insulation Shield (EIS): • Thermoset semi-conducting polymeric layer free stripping from insulation Metallic Shield: • 5 mil annealed copper tape with an overlap of 25% Jacket: • Low-friction, lead-free, flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC) Options: • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 CATALOG NUMBER (AWG/ kcmil) 17031.130208* 2 17031.130108* 1 17031.135108 1/0 17031.135208* 2/0 17031.135308* 3/0 17031.135408 4/0 17031.136008* 250 17031.136208 350 17031.136508 500 17031.137008 750 17031.137508 1000 COND. SIZE CONDUCTOR DIAMETER INCHES 0.27 0.31 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 NOMINAL INSULATION DIAMETER INCHES THICKNESS NOMINAL JACKET Applications: • Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial three-phase applications • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4(A)(5) Features: • Rated at 105˚C • High Speed low friction technology for easy cable pulling • Excellent heat, moisture and sunlight resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant NOMINAL CABLE DIAMETER WEIGHT ALUMINUM WEIGHT COPPER WEIGHT 0.710 0.800 0.080 2.03 0.99 25.14 0.745 0.830 0.080 2.03 1.02 25.91 0.780 0.865 0.080 2.03 1.06 26.92 0.820 0.905 0.080 2.03 1.10 27.94 0.865 0.955 0.080 2.03 1.14 28.95 0.920 1.005 0.080 2.03 1.21 30.73 0.970 1.060 0.080 2.03 1.25 31.75 1.070 1.155 0.080 2.03 1.35 34.29 1.190 1.275 0.080 2.03 1.47 37.34 1.370 1.460 0.080 2.03 1.65 41.91 1.06 1.520 1.610 0.110 2.79 1.86 47.24 , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS 515 553 598 652 718 807 869 1031 1255 1621 2068 Dimensions and weights are nominal. Subject to industry tolerances. * Non-stock item; minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310.60(C)(74) of the NEC for triplexed or three single conductor aluminum cables in isolated conduit in air based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310.60(C)(78) of the NEC for triplexed or three single conductor aluminum cables in underground ducts (three conductors per duct), based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392.80(B)(2) of the NEC at an ambient air temperature of 40˚C (104˚F) the ampacities are based on 75% of the values per Table 310.60(C)(70), operating temperature denoted in column header. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 70% of the values per Table 310.60(C)(70). (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered but should be checked for individual installations. ¥ 100% insulation level is available upon request. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE”. b) The NESC Lightning bolt symbol is on all Uniblend® constructions. 767 822 890 970 1068 1201 1293 1534 1868 2412 3078 62 78 99 125 158 199 234 329 468 703 937 92 116 147 186 235 296 348 490 696 1046 1394 CONDUIT IN AIR (1) Compliances: • National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC, UL File # E90501 • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA Acceptable • RoHS Compliant Packaging: • Material cut to length and shipped on non- returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing AMPACITY UNDERGROUND DUCT (2) TRAY (3) MIN. MAX. INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km LBS/1000 FT kg/km 90˚C 105˚C 90˚C 105˚C 90˚C 105˚C 15 kV¥ 71 74 77 81 85 90 94 103 113 129 140 106 115 130 120 130 110 130 150 135 115 150 170 155 121 175 200 175 126 200 225 200 134 230 260 230 140 255 290 250 145 165 190 215 245 270 153 310 350 305 330 168 385 430 370 192 485 540 455 208 565 640 525 - - - - 150 170 175 195 205 225 235 265 260 290 325 360 400 400 450 490 565 515 585 620 705 SIZING (4) (INCHES) 3 3.5 3.5 3.5 3.5 4 4 5 5 6 6 CONDUIT Phone: 888-593-3355 www.generalcable.com