SPEC 6375 September, 2016 Uniblend CPE High Speed ® EPR/Copper Tape Shield/CPE, Medium-Voltage Power, Shielded 15 kV, UL Type MV-105, 133% Ins. Level, 220 Mils Product Construction: Conductor: • 2 AWG thru 1000 kcmil annealed bare copper compact Class B strand Extruded Strand Shield (ESS): • Extruded thermoset semi-conducting stress- control layer over conductor Insulation: • Lead-free Ethylene Propylene Rubber (EPR) insulation, contrasting in color to the black semi-conducting shield layers Extruded Insulation Shield (EIS): • Thermoset semi-conducting polymeric layer free stripping from insulation Metallic Shield: • 5 mil annealed copper tape with an overlap of 25% Jacket: • Flame-retardant, moisture- and sunlight-resistant Chlorinated Polyethylene (CPE) Options: • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 Applications: • Superior performance in petrochemical plants, pulp and paper mills, sewage and water treatment plants, environmental protection systems, railroads, mines, utility power generating stations, steel mills, textile plants and other industrial three-phase applications Applications (cont’d.): • For use in wet or dry locations when installed in accordance with NEC • For use in aerial, conduit, open tray and underground duct installations • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4(A)(5) Features: • Rated at 105˚C • Excellent flame resistance – burns to an ash; does not exhibit thermoplastic drip • Excellent heat, moisture and sunlight resistance • Excellent flame resistance • Outstanding corona resistance • Flexibility for easy handling • High Speed low friction technology for easy cable pulling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C • 105°C rating for continuous operation • 140°C rating for emergency overload conditions • 250°C rating for short circuit conditions CATALOG NUMBER 17131.130205 17131.130105 17131.135105 17131.135205 17131.135305* 17131.135405 17131.136005 17131.136205 17131.136505 17131.137005 17131.637505 (AWG/ kcmil) 2 1 1/0 2/0 3/0 4/0 250 350 500 750 1000 COND. SIZE CONDUCTOR DIAMETER INCHES 0.27 0.31 0.34 0.38 0.43 0.48 0.53 0.62 0.74 0.91 NOMINAL INSULATION DIAMETER INCHES MIN. MAX. NOMINAL CABLE NOMINAL JACKET THICKNESS DIAMETER WEIGHT COPPER WEIGHT 0.710 0.800 0.080 2.03 0.745 0.830 0.080 2.03 0.780 0.865 0.080 2.03 0.820 0.905 0.080 2.03 0.865 0.955 0.080 2.03 0.920 1.005 0.080 2.03 0.970 1.060 0.080 2.03 1.070 1.155 1.06 1.520 1.610 , UL TYPE MV-105, 133% INS. LEVEL, 220 MILS 0.99 25.14 0.080 2.03 1.190 1.275 0.080 2.03 1.370 1.460 0.080 2.03 0.110 2.79 1.02 25.91 1.06 26.92 1.10 27.94 1.14 28.95 1.21 30.73 1.25 31.75 1.35 34.29 1.47 37.34 1.65 41.91 1.86 47.24 Dimensions and weights are nominal. Subject to industry tolerances. * Non-stock item; minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310.60(C)(73) of the NEC for triplexed or three single conductor copper cables in isolated conduit in air based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310.60(C)(77) of the NEC for triplexed or three single conductor copper cables in underground ducts (three conductors per duct), based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on single conductor Type MV-105 sizes #1/0 AWG and larger in an uncovered tray in accordance with Section 392.80(B)(2) of the NEC at an ambient air temperature of 40˚C (104˚F) the ampacities are based on 75% of the values per Table 310.60(C)(69), operating temperature denoted in column header. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 70% of the values per Table 310.60(C)(69). (4) Based on nominal cable diameters, three single cables in the duct (PVC Schedule 40) with no ground wire and a maximum of 40% fill. Jam ratio has been considered but should be checked for individual installations. ¥ 100% insulation level is available upon request. Note: a) Sizes smaller than 1/0 AWG do not include “FOR CT USE”. b) The NESC Lightning bolt symbol is on all Uniblend® constructions. 655 730 820 933 1072 1248 1402 1778 2325 3250 4209 975 1086 1220 1388 1595 1857 2086 2646 3460 4836 6263 276 332 403 492 603 743 866 1184 1657 2445 3228 CONDUIT IN AIR (1) Compliances: • National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • AEIC CS8 • UL listed as Type MV-105 for use in accordance with NEC, UL File # E90501 • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA Acceptable • RoHS Compliant Packaging: • Material cut to length and shipped on non- returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing AMPACITY UNDERGROUND DUCT (2) INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km 90˚C 105˚C 90˚C 15 kV¥ 411 150 494 170 600 195 165 190 215 732 225 255 897 260 1105 295 290 330 1289 330 365 655 155 175 200 230 260 295 325 1761 395 440 390 2466 480 535 3638 585 4803 675 755 465 565 640 105˚C 165 185 215 245 275 315 345 TRAY (3) 90˚C 105˚C - - 195 - - 220 225 250 260 300 335 415 415 500 610 690 515 665 290 335 370 460 575 745 795 890 SIZING (4) (INCHES) 3 3.5 3.5 3.5 3.5 4 4 5 5 6 6 CONDUIT Phone: 888-593-3355 www.generalcable.com 3/2017