SPEC 7200 September, 2016 Duralox ® EPR/AIA/PVC, Power, Nonshielded, Armored 2400 V, UL Type MV-90 or MC, Three Conductor Product Construction: Conductors: • 6 AWG thru 1000 kcmil bare copper, compact Class B strand Extruded Strand Shield (ESS): • Extruded thermoset semi-conducting stress control layer over conductor Insulation: • Ethylene Propylene Rubber (EPR), colored to contrast with black conducting shield layer Ground: • Annealed bare copper Class B stranding per ASTM B8 Armor: • Aluminum Interlocked Armor (AIA) Jacket: • Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), yellow Options: • Galvanized Steel Interlocked Armor (GSIA) CATALOG NUMBER 17471.580600* 17471.580400* 17471.580200 17471.585100* 17471.585200 17471.585400 17471.586000* 17471.586200 17471.586500 17471.587000* 17471.587500* COND. 3 3 3 3 3 3 3 3 3 3 3 NO. OF (AWG) 6 4 2 0.34 4 0.115 2.92 1.61 41.0 0.060 1.52 1.74 44.3 1118 1665 2003 2982 0.38 4 0.115 2.92 1.71 43.3 0.060 1.52 1.84 46.6 1376 2049 2326 3463 0.48 3 0.115 2.92 1.92 48.7 0.060 1.52 2.05 52.0 2143 3191 3256 4848 250 0.52 3 0.115 2.92 2.00 50.7 0.060 1.52 2.13 54.1 2503 3727 3689 5493 350 0.62 2 0.115 2.92 2.21 56.0 0.060 1.52 2.34 59.3 3479 5180 4825 7184 500 0.74 1 0.115 2.92 2.46 62.6 0.075 1.91 2.63 66.7 4933 7345 6567 9778 750 0.91 1/0 0.115 2.92 2.83 72.0 0.075 1.91 3.00 76.1 7347 10940 9320 13877 1000 1.07 1/0 0.115 2.92 3.16 80.3 0.085 2.16 3.35 85.0 9680 14414 12023 17902 1/0 2/0 4/0 Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item; minimum runs apply. Please consult Customer Service for price and delivery. COND. SIZE INCHES (AWG) INCHES mm INCHES mm INCHES mm INCHES mm LBS/1000 FT kg/km LBS/1000 FT kg/km 6 AWG - 1000 kcmil CONDUCTORS - 115 MILS INS. 0.17 6 0.115 2.92 1.16 29.4 0.050 1.27 1.27 32.2 0.21 6 0.115 2.92 1.26 31.9 0.050 1.27 1.37 34.7 0.27 6 0.115 2.92 1.37 34.8 0.050 1.27 1.48 37.6 327 473 487 854 1272 704 1056 1572 703 1047 1363 2030 COND. DIA. GRND. WIRE SIZE Applications: • Ideally suited for use in a broad range of commercial, industrial and utility applications where reliability is the major concern, maximum performance will be demanded, space is limited, ease of installation is critical and fire resistance is necessary • May be installed in wet or dry locations, indoors or outdoors, direct burial and in exposed or concealed work • May be used in cable trays or on approved supports in protected areas • Permitted for use per NEC Article 330 - Class I, Division 2 - Class II, Division 2 - Class III, Divisions 1 and 2 Features: • Rated at 90˚C wet or dry • Excellent heat and moisture resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss INSULATION THICKNESS MINIMUM NOM. DIA. (OVER) ARMOR THICKNESS NOMINAL JACKET Features (cont'd.): • Chemical- and radiation-resistant • Excellent crush resistance • Flame or sunlight resistance • Cost-effective alternative to installations in conduit • Meets cold bend test at -40˚C • 90°C rating for continuous operation • 130°C rating for emergency overload conditions • 250°C rating for short circuit conditions • Sunlight-resistant for CT use Compliances: Industry Compliances: • UL 1569 • UL 1072 • ICEA S-96-659/NEMA WC71 • UL Type MV-90, UL File # E90501 • UL Type MC, UL File # E90496 Flame Test Compliances: • IEEE 383 (70,000 BTU/hr) • UL 1685 (70,000 BTU/hr) • IEEE 1202 (70,000 BTU/hr) CSA FT4 • ICEA T-29-520 (210,000 BTU/hr) • ICEA T-30-520 (70,000 BTU/hr) Other Compliances: • EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA Acceptable Packaging: • Material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing NOMINAL CABLE O.D. COPPER WEIGHT WEIGHT NET Phone: 888-593-3355 www.generalcable.com