SPEC 8450 September, 2016 HVTECK TRXLPE/Tape Shield/PVC/AIA/PVC, Power, Shielded, Armored 15 kV, CSA HVTECK, 133% Ins. Level, 220 Mils, Three Conductor Product Construction: Conductor: • 2 AWG thru 750 kcmil bare copper compact Class B strand Strand Shield: • A thermoset semi-conducting strand shield is extruded over the conductor Insulation: • Tree-Retardant Cross-linked Polyethylene (TRXLPE) Insulation Shield: • This consists of a semi-conducting thermosetting layer, applied in a triple extrusion process, plus a helically applied gapped copper tape • Color-coded: black, red or blue colored tape placed longitudinally under the copper tape shield Ground (Bonding) Conductor: • The conductor consists of one uninsulated stranded bare copper conductor Inner Jacket: • Lead-free, flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black Armor: • Aluminum Interlocked Armor (AIA) Overall Jacket: • Lead-free, ACID-FLAME-CHECK ✓✓® flame- retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), red NOMINAL DIAMETER (OVER) CATALOG NUMBER COND. 17496.230200* 3 17496.010100* 3 17451.316781* 3 17496.015200* 3 17496.025300* 3 17496.055400 3 17496.026000* 3 17496.046200 3 17496.056500 3 17496.037000 3 NO. OF (AWG/ kcmil) COND. SIZE GROUND WIRE SIZE 1/0 2/0 3/0 4/0 250 350 500 750 6 6 6 6 4 4 4 3 3 2 INSULATION INSULATION SHIELD INNER JACKET ARMOR CABLE (AWG) INCHES mm INCHES mm INCHES mm INCHES mm INCHES mm 1000 FT LBS/ kg/ km Options: • Galvanized Steel Interlocked Armor (GSIA) Applications: • For wiring in all hazardous locations when used with certified HL cable glands • For exposed and concealed wiring in dry, damp or wet locations • For use in ventilated, non-ventilated and ladder- type cable trays in dry, damp or wet locations • For direct earth burial (with protection as required by inspection authority) Features: • Rated at 90˚C wet or dry • Excellent crush, oil and chemical resistance • Provides long service life • Cost-effective alternative to installations in conduit • Meets cold bend and impact tests at -40˚C Compliances: Industry Compliances: • CSA Standard C68.10 Compliances (cont'd.): Flame Test Compliances: • CSA FT1 and FT4 • IEEE 383 (70,000 BTU/hr) • UL 1581 (70,000 BTU/hr) • IEEE 1202 (70,000 BTU/hr) CSA FT4 • ICEA T-30-520 (70,000 BTU/hr) • ICEA T-29-520 (210,000 BTU/hr) Other Compliances: • Hazardous Location Rating: HL • EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA Acceptable • RoHS Compliant Packaging: • For Canadian customers, lengths are provided on returnable wood or steel reels that require a deposit. Extra charges apply for lagging, pulling eyes, paralleling and plexing • For U.S. customers, material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing COPPER WEIGHT NET WEIGHT W/ARMOR LBS/1000 FT kg/km AL STEEL AL STEEL 2 AWG THRU 750 kcmil—THREE CONDUCTOR—133% INS. LEVEL, 220 MILS INS. (5.59 mm)—15 kV 2 1 0.76 19.3 0.83 21.1 2.02 51.3 2.31 58.7 2.43 61.7 793 1180 2665 3518 3966 5235 0.79 20.1 0.86 21.9 2.10 53.3 2.37 60.2 2.49 63.3 964 1435 3089 3930 4597 5850 0.83 21.1 0.89 22.6 2.17 55.1 2.46 62.5 2.58 65.6 1175 1749 3300 4300 4900 6390 0.86 21.8 0.93 23.6 2.26 57.3 2.55 64.8 2.67 67.8 1438 2140 3650 4690 5430 6980 0.91 23.0 0.98 24.9 2.36 60.0 2.65 67.3 2.77 70.4 1821 2710 4140 5230 6160 7780 0.96 24.3 1.03 26.2 2.47 62.8 2.76 70.1 2.88 73.2 2248 3345 4680 5810 6960 8650 1.02 25.8 1.08 27.5 2.59 65.8 2.88 73.2 3.00 76.2 2607 3880 5275 6440 7850 9580 1.12 28.3 1.20 30.5 2.90 73.7 3.19 81.0 3.33 84.6 3597 5353 6842 8170 10181 12160 1.24 31.5 1.32 33.6 3.16 80.3 3.45 87.6 3.59 91.2 5022 7474 8513 10050 12668 14950 1.42 36.0 1.51 38.3 3.57 90.7 3.85 97.8 4.00 101.6 7452 11090 11507 13160 17122 19580 Dimensions and weights are nominal; subject to industry tolerances. *Non-stock item; minimum runs apply. Please consult Customer Service for price and delivery. ** Ampacities at other voltage levels do not vary significantly. Special approval by local electrical inspection authorities may be required (Ref. CE Code Part 1, Appendix B, Rule 4-004). AMPACITY** (40˚C AMBIENT) 141 161 184 212 242 278 306 373 450 545 OUTDOOR Phone: 888-593-3355 www.generalcable.com (10/2017)
Powered by Prysmian North America
Industrial Cable
Title Name |
Pages |
Delete |
Url |
Empty |
Search Text Block
Page #page_num
#doc_title
Hi $receivername|$receiveremail,
$sendername|$senderemail wrote these comments for you:
$message
$sendername|$senderemail would like for you to view the following digital edition.
Please click on the page below to be directed to the digital edition:
$thumbnail$pagenum
$link$pagenum
Your form submission was a success. You will be contacted by Washington Gas with follow-up information regarding your request.
This process might take longer please wait