SPEC A001 October, 2014 CCW Installation Manual ® CCW Type MC-HL CCW Type MC-HL contains separate equipment grounding conductor(s) sized in accordance with 250.122 in all constructions, in addition to the standard gas/vapor-tight continuously corrugated metallic sheath and overall jacket of suitable polymeric materials and complies with UL 2225, Standard for Cables and Cable Fittings For Use In Hazardous (Classified) Locations. UL 2225 also includes additional requirements that the cable comply with a -40°C low temperature impact test, more severe room temperature crush and impact tests, and a more severe vertical tray flame test. When installed with termination fittings listed for the application, CCW MC-HL may be used in industrial establishments with restricted public access, where the conditions of maintenance and supervision ensure that only qualified persons service the installation. In addition to all the uses permitted for CCW Type MC, CCW Type MC-HL is also permitted to be installed in the following hazardous (classified) locations: Class I, Division 1 [501.10(A)(1)(c)] Class I, Zone 1 [505.15(B)(1)(b)] Class II, Division 1 [502.10(A)(1) and (3)] Zones 20 and 21 [506.15(A)(3) and (B)(1)] [Not included in UL 2225] CCW Type MV or MC CCW Type MV or MC contains conductors rated 105°C and is available from 2400 V to 35 kV. The cable complies with both UL 1569, Metal- Clad Aluminum Cable, and UL 1072, Medium-Voltage Power Cables, and is listed and marked as Type MV or MC. The cable is permitted to be used in accordance with 328.10 and 330.10 and installed in the same applications as CCW Type MC. CCW Remote-Control, Signaling, and Power-Limited Cables CCW Type MC and CCW Type MC- HL are permitted to be used on 600 V Class 1 power-limited circuits, Class 1 remote-control and signaling circuits, and the supply side of Class 2 or Class 3 power sources in the applications and locations shown above for the applicable cable type, subject to any limitations specified in Part II of Article 725, also see 725.127. Type MC cable is permitted to be installed in compliance with Parts II and III of Article 725 and 770.133 as applicable and in accordance with 330.10(B)(1) through (B)(4). CCW Type ITC-HL CCW Instrumentation Tray Cable Type ITC-HL is permitted to be installed in accordance with Article 501.10(A)(1)(d) in Class l, Zone 1 or Division 1 locations. All constructions are manufactured with the standard gas/vapor tight continuously corrugated metallic sheath and covered with a jacket of suitable polymeric material. CCW Type ITC-HL cable complies with UL 2225, Standard for Cables and Cable Fittings For Use In Hazardous (Classified) Locations. The CCW sheath provides equipment grounding through the sheath. UL 2225 also includes additional requirements that the cable comply with the -40°C low temperature impact test, more severe room temperature crush and impact tests, and a more severe vertical tray flame test. In addition to all the applications permitted for CCW Type ITC, CCW Type ITC-HL is also permitted in the following additional hazardous (classified) locations: Class I, Division 1 [501.10(A)(1)(d)] Class I, Zone 1 [505.15(B)(1)(c)] CCW Type ITC-HL/PLTC (Instrumentation Tray Cable/ Power-Limited Tray Cable) CCW Type ITC-HL/PLTC is permitted in 727.4 to be used as ITC cable on instrumentation and control circuits operating at 150 volts or less and 5 amperes or less in industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons service the installation: • In cable trays • In raceways • In the following hazardous (classified) locations: Class I, Division 2 [501.10(B)(1), (3) and (4)] Class I, Zone 2 [505.15(C)(1)(c) and (d)] Class II, Division 2 [502.10(B)(1), (4) and (5)] Intrinsically Safe Circuits [504.20] Zone 22 [506.15(C)(4) and (5)] [Not included in UL 2225] Commercial garages [511.7] • As aerial cable on a messenger • Direct buried • Under raised floors in rooms contain- ing industrial process control equip- ment and rack rooms • Under raised floors in information technology equipment rooms – see Table 645.5. Refer to Article 727 for complete wiring methods, installation requirements, and listing requirements for CCW Type ITC- HL cables. Unless otherwise stated, all references refer to the 2014 NEC® . Phone: 888-593-3355 www.generalcable.com