44 Industrial Cables Uniblend® PVC EPR/Copper Tape Shield with Overall PVC Jacket, Medium-Voltage Power, Shielded, 5 kV and 8 kV EASY GLIDER ® Product Construction: Conductor: • 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand Extruded Strand Shield (ESS): • Extruded thermoset semi-conducting stress- control layer over conductor Insulation: • Lead-free Ethylene Propylene Rubber (EPR) insulation, contrasting in color to the black semi-conducting shield layers Extruded Insulation Shield (EIS): • Thermoset semi-conducting polymeric layer free stripping from insulation Metallic Shield: • Annealed copper tape with an overlap of 25% Grounding Conductor: • 1 bare grounding conductor may be in contact with metallic shielding tape Overall Jacket: • Low-friction, lead-free, flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC) Options: • STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610 • 3 bare copper ground wires • Covered ground wires Applications: • Suited for use in a broad range of commercial, industrial and utility applications, where reliability is the major concern, space is limited and ease of installation is critical Compliances (cont'd): • CSA C22.2 No. 230 Type TC-ER (Sizes 1/0 AWG and larger) • UL listed as Type MV-105 for use in accordance with NEC, UL File # E518856 • UL 1685 (Sizes 1/0 AWG and larger) UL Flame Exposure Test • UL 1685 Vertical Flame and ST1 Smoke Release Test • Sizes 1/0 AWG and larger are listed and marked “Sunlight-Resistant FOR CT USE” in accordance with NEC • IEEE 1202 (70,000 BTU/hr)/CSA FT4 • EPA 40 CFR, Part 261 for leachable lead content per TCLP method • OSHA Acceptable • RoHS Compliant Packaging: • Material cut to length and shipped on non- returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit • Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and triplexing SPEC 6255 Feb, 2025 CATALOG NUMBER COND. SIZE (AWG/ kcmil) NOMINAL CONDUCTOR DIAMETER INSULATION DIAMETER INCHES GROUND WIRE (AWG) NOMINAL JACKET THICKNESS NOMINAL CABLE COPPER WEIGHT AMPACITY DIAMETER WEIGHT CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3) INCHES MIN. MAX. IN mm IN mm LBS/ 1000 FT kg/ km LBS/ 1000 FT kg/ km 90˚C 105˚C 90˚C 105˚C 90˚C 105˚C 5 kV AND 8 kV, UL TYPE MV-105, 133%/100% INS. LEVELS, 115 MILS 15493.400605 6 0.17 0.415 0.490 6 0.080 2.03 1.32 33.53 1009 1502 454 676 83 92 88 95 93 105 15493.400405 4 0.21 0.455 0.535 6 0.080 2.03 1.41 35.81 1245 1852 611 909 105 120 115 125 120 135 15493.400205 2 0.27 0.510 0.590 6 0.080 2.03 1.53 38.86 1565 2330 853 1270 145 165 150 160 165 185 15493.405105 1/0 0.34 0.580 0.655 4 0.080 2.03 1.67 42.42 2091 3112 1283 1909 195 215 195 210 215 240 15493.405205 2/0 0.38 0.620 0.695 4 0.080 2.03 1.76 44.70 2392 3559 1549 2305 220 245 220 235 245 275 15493.405405 4/0 0.48 0.720 0.795 3 0.110 2.79 2.06 52.32 3517 5233 2338 3479 290 320 285 305 325 360 15493.406005 250 0.52 0.770 0.850 2 0.110 2.79 2.18 55.37 3990 5938 2751 4094 315 350 310 335 360 400 15493.406205 350 0.62 0.870 0.945 2 0.110 2.79 2.38 60.45 5052 7519 3706 5515 385 430 375 400 435 490 15493.406505 500 0.74 0.990 1.065 1 0.110 2.79 2.63 66.80 6684 9947 5178 7705 470 525 450 485 535 600 15493.407005 750 0.91 1.170 1.250 1/0 0.140 3.56 3.05 77.47 9499 14136 7621 11341 570 635 545 585 670 745 15493.407505 1000 1.06 1.320 1.400 2/0 0.140 3.56 3.48 88.39 12601 18752 10070 14986 650 725 615 660 770 860 Dimensions and weights are nominal. Subject to industry tolerances. * Non-stock item; minimum runs apply. Please consult Customer Service for price and delivery. (1) Ampacities are in accordance with Table 310.60(C)(75) of the NEC for three conductor copper cable in isolated conduit in air based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient air temperature of 40˚C (104˚F). (2) Ampacities are in accordance with Table 310.60(C)(79) of the NEC for three conductor copper cable in underground ducts (three conductors per duct), based on a conductor temperature of 90˚C (194˚F) or 105˚C (221˚F), temperature denoted in column header, and an ambient earth temperature of 20˚C (68˚F), electrical duct arrangement per Figure 310.60 Detail 1, 100% load factor, and earth thermal resistance (rho) of 90. (3) Ampacities are based on three conductor Type MV-105 cables in single layer in an uncovered tray with maintained spacing of not less than one cable diameter between cables, in accordance with Section 392.80(B)(1) of the NEC at an ambient air temperature of 40°C (104°F); the ampacities are per Table 310.60(C)(71), operating temperature denoted in column header. For cable trays with unventilated covers for more than 6 feet, the ampacities shall not exceed 95% of the values in NEC Table 310.60(C)(75). Note: a) All sizes are “FOR CT USE”. b) The NESC Lightning bolt symbol is on all Uniblend® constructions. Applications (cont'd): • In wet or dry locations when installed in accordance with NEC • In aerial, direct burial, conduit, open tray and underground duct installations Features: • Rated at 105˚C • Easy Glider® low friction technology for easy cable pulling • Excellent heat, moisture and sunlight resistance • Outstanding corona resistance • Flexibility for easy handling • High dielectric strength • Low moisture absorption • Electrical stability under stress • Low dielectric loss • Chemical-resistant • Meets cold bend test at -35˚C • 105°C rating for continuous operation • 140°C rating for emergency overload conditions • 250°C rating for short circuit conditions Compliances: • National Electrical Code (NEC) • UL 1072 • ICEA S-93-639/NEMA WC74 • ICEA S-97-682 • ICEA T-33-655 • AEIC CS8 • CSA C68.10